for Serial#: 6662391
Address: 6263 N TEUTONIA AV

Taxkey: 159-9990-100


Description Detail
1 Electrical permit required
.
2 Replace flex cords with fixed wiring
(At candy case - 1st floor) /
3 Box required
(1st floor) /
4 Support conduit
(1st floor & 2nd floor mezzanine) /
5 Provide missing covers
(1st floor & 2nd floor mezzanine) /
6 Close unused openings in boxes, housing, etc.
(1st floor & 2nd floor mezzanine) /
7 Identify feeder or branch circuits
(NEC 408.4).. Label all breakers - in detail, accurately, legibly & completely as well as all disconnects & panels - 1st floor. /
8 Custom violation
(NEC 424.19(B)1).. Install breaker locks for baseboard heaters capable of being locked in open position - 1st floor. / 222.01 /Comm 16.18 /
9 Custom violation
(NEC 348.30).. Secure/support all flex properly - 1st floor & 2nd floor mezzanine. / 222.01 /Comm 16.18 /
10 Custom violation
(NEC 350.30).. Secure/support all liquid tight properly - outside. / 222.01 /Comm 16.18 /
11 Custom violation
(NEC 424.19).. Install disconnect for unit heaters - 1st floor & 2nd floor mezzanine. / 222.01 /Comm 16.18 /
12 Custom violation
(NEC 430.102).. Provide disconnects for motors for recirculating pumps in same room as sprinkler controllers - 1st floor. / 222.01 /Comm 16.18 /
13 Custom violation
(NEC 314.22).. Cannot install conduit into exterior surface cover - far box/light on south side of building exterior. / 222.01 /Comm 16.18 /
14 Custom violation
(NEC 110.26).. Provide proper clearance about electrical equipment and on entrance/pathway to each, of sufficient area - 1st floor. / 222.01 /Comm 16.18 /
15 Custom violation
(NEC 410.29).. Properly wire show cases, at candy etc - 1st floor. / 222.01 /Comm 16.18 /
16 Custom violation
(NEC 220.43(B).. Circuit track lighting properly - 1st & 2nd floor. / 222.01 /Comm 16.18 /
17 Custom violation
(NEC 410.104).. Fasten/secure track lighting properly - 1st & 2nd floor. / 222.01 /Comm 16.18 /
18 Custom violation
(NEC 600.6 & 600.5(A).. Provide disconnect at each neon sign/outline lighting - interior of building - 1st & 2nd floor. / 222.21 /
19 Custom violation
Please make sure all track lighting is also labeled completely, including neon lighting - 1st & 2nd floor. / NOTE: /
20 Custom violation
Original inspection date was 06/11/07. / NOTE: /