| Description |
Detail |
1 Electrical permit required
|
. |
2 Replace flex cords with fixed wiring
|
. |
3 Box required
|
. |
4 Support conduit
|
. |
5 Provide missing covers
|
. |
6 Close unused openings in boxes, housing, etc.
|
. |
7 Identify feeder or branch circuits
|
(NEC 408.4).. Label all breakers, in detail, accurately, legibly & completely - as well as all disconnects & panels. / |
8 Custom violation
|
(NEC 424.19(B)1.. Install breaker locks for baseboard heaters capable of being locked in open position.l / 222.01 /Comm 16.18 / |
9 Custom violation
|
(NEC 348.30).. Secure/support all flex properly. / 222.01 /Comm 16.18 / |
10 Custom violation
|
(NEC 350.30).. Secure/support all liquid tight properly. / 222.01 /Comm 16.18 / |
11 Custom violation
|
(NEC 424.19).. Install disconnect for unit heaters. / 222.01 /Comm 16.18 / |
12 Custom violation
|
(NEC 430.102).. Provide disconnects for motors for recirculating pumps in same room as sprinkler controllers. / 222.01 /Comm 16.18 / |
13 Custom violation
|
(NEC 314.22).. Cannot install conduit into exterior surface cover fan box/light on south side of building. / 222.01 /Comm 16.18 / |
14 Custom violation
|
(NEC 110.26).. Provide proper clearance about electrical equipment and an entrance/pathway to each of sufficient area. / 222.01 /Comm 16.18 / |
15 Custom violation
|
(NEC 410.29).. Properly wire show cases, at candy etc. / 222.01 /Comm 16.18 / |
16 Custom violation
|
(NEC 220.43(B).. Circuit track lighting properly. / 222.01 /Comm 16.18 / |
17 Custom violation
|
(NEC 410.104).. Fasten/secure track lighting properly. / 222.01 /Comm 16.18 / |
18 Custom violation
|
(NEC 600.6, 600.5(A).. Provide disconnect at each neon sign/outline lighting on interior of building. / 222.21 / |
19 Custom violation
|
Please make sure all track lighting is also labeled completely, including neon lighting. / NOTE: / |